Post on 01-Jul-2015
description
Project 1
22.05.2014
OperatorTelephone
Faxe-Mail
Table of contents
Project 1Table of contents 1LED street lights
Luminaire Data Sheet 2Street 1
Planning data 3Luminaire parts list 4False Color Rendering 5Valuation Fields
Valuation Field Roadway 2Results overview 6Isolines (E) 7Value Chart (E) 8Observer
Observer 3Isolines (L) 9
Observer 4Isolines (L) 10
Observer 5Isolines (L) 11
Valuation Field Emergency Lane 1Isolines (E) 12
Page 1
Project 1
22.05.2014
OperatorTelephone
Faxe-Mail
LED street lights / Luminaire Data Sheet
See our luminaire catalog for an image of the luminaire.
Luminous emittance 1:
Luminaire classification according to CIE: 99CIE flux code: 41 77 97 99 100
Due to missing symmetry properties, no UGR table can be displayed for this luminaire.
Page 2
Project 1
22.05.2014
OperatorTelephone
Faxe-Mail
Street 1 / Planning data
Street Profile
Light loss factor: 0.95
Emergency Lane 2 (Width: 3.000 m)
Roadway 2 (Width: 12.000 m, Number of lanes: 3, tarmac: R3, q0: 0.070)
Median 1 (Width: 1.000 m, Height: 0.800 m)
Roadway 1 (Width: 12.000 m, Number of lanes: 3, tarmac: R3, q0: 0.070)
Emergency Lane 1 (Width: 3.000 m)
Luminaire Arrangements
Luminaire: LED street lightsLuminous flux (Luminaire): 24999 lm Maximum luminous intensities
at 70°: 644 cd/klmat 80°: 290 cd/klmat 90°: 7.74 cd/klmAny direction forming the specified angle from the downward vertical, with
the luminaire installed for use.
Arrangement complies with glare index class D.6.
Luminous flux (Lamps): 25000 lmLuminaire Wattage: 250.0 WArrangement: Double row, opposingPole Distance: 40.000 mMounting Height (1): 12.000 mHeight: 12.000 mOverhang (2): -1.000 mBoom Angle (3): 15.0 °Boom Length (4): 2.500 m
Page 3
Project 1
22.05.2014
OperatorTelephone
Faxe-Mail
Street 1 / Luminaire parts list
LED street lights (Type 1) Article No.: Luminous flux (Luminaire): 24999 lmLuminous flux (Lamps): 25000 lmLuminaire Wattage: 250.0 WLuminaire classification according to CIE: 99CIE flux code: 41 77 97 99 100Fitting: 1 x User defined (Correction Factor 1.000).
See our luminaire catalog for an image of
the luminaire.
Page 4
Project 1
22.05.2014
OperatorTelephone
Faxe-Mail
Street 1 / False Color Rendering
Page 5
Project 1
22.05.2014
OperatorTelephone
Faxe-Mail
Street 1 / Valuation Field Roadway 2 / Results overview
Light loss factor: 0.95 Scale 1:329
Grid: 14 x 9 Points Accompanying Street Elements: Roadway 2.tarmac: R3, q0: 0.070Selected Lighting Class: ME1 (Not all lighting performance requirements are met.)
Lav [cd/m²] U0 Ul TI [%] SR
Calculated values: 2.09 0.62 0.80 11 0.87Required values according to class: ≥ 2.00 ≥ 0.40 ≥ 0.70 ≤ 10 ≥ 0.50
Fulfilled/Not fulfilled:
Assigned observer (3 Pieces):
No. Observer Position [m] Lav [cd/m²] U0 Ul TI [%]
1 Observer 3 (-60.000, 15.000, 1.500) 2.40 0.62 0.80 8
2 Observer 4 (-60.000, 19.000, 1.500) 2.26 0.66 0.88 10
3 Observer 5 (-60.000, 23.000, 1.500) 2.09 0.74 0.91 11
Page 6
Project 1
22.05.2014
OperatorTelephone
Faxe-Mail
Street 1 / Valuation Field Roadway 2 / Isolines (E)
Values in Lux, Scale 1 : 329
Grid: 14 x 9 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax
34 23 45 0.698 0.516
Page 7
Project 1
22.05.2014
OperatorTelephone
Faxe-Mail
Street 1 / Valuation Field Roadway 2 / Value Chart (E)
Values in Lux, Scale 1 : 329Not all calculated values could be displayed.
Grid: 14 x 9 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax
34 23 45 0.698 0.516
Page 8
Project 1
22.05.2014
OperatorTelephone
Faxe-Mail
Street 1 / Valuation Field Roadway 2 / Observer 3 / Isolines (L)
Values in Candela/m², Scale 1 : 329
Grid: 14 x 9 Points Observer Position: (-60.000 m, 15.000 m, 1.500 m) tarmac: R3, q0: 0.070
Lav [cd/m²] U0 Ul TI [%]
Calculated values: 2.40 0.62 0.80 8
Required values according to class ME1: ≥ 2.00 ≥ 0.40 ≥ 0.70 ≤ 10
Fulfilled/Not fulfilled:
Page 9
Project 1
22.05.2014
OperatorTelephone
Faxe-Mail
Street 1 / Valuation Field Roadway 2 / Observer 4 / Isolines (L)
Values in Candela/m², Scale 1 : 329
Grid: 14 x 9 Points Observer Position: (-60.000 m, 19.000 m, 1.500 m) tarmac: R3, q0: 0.070
Lav [cd/m²] U0 Ul TI [%]
Calculated values: 2.26 0.66 0.88 10
Required values according to class ME1: ≥ 2.00 ≥ 0.40 ≥ 0.70 ≤ 10
Fulfilled/Not fulfilled:
Page 10
Project 1
22.05.2014
OperatorTelephone
Faxe-Mail
Street 1 / Valuation Field Roadway 2 / Observer 5 / Isolines (L)
Values in Candela/m², Scale 1 : 329
Grid: 14 x 9 Points Observer Position: (-60.000 m, 23.000 m, 1.500 m) tarmac: R3, q0: 0.070
Lav [cd/m²] U0 Ul TI [%]
Calculated values: 2.09 0.74 0.91 11
Required values according to class ME1: ≥ 2.00 ≥ 0.40 ≥ 0.70 ≤ 10
Fulfilled/Not fulfilled:
Page 11
Project 1
22.05.2014
OperatorTelephone
Faxe-Mail
Street 1 / Valuation Field Emergency Lane 1 / Isolines (E)
Values in Lux, Scale 1 : 329
Grid: 14 x 3 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax
29 21 43 0.718 0.482
Page 12