1
www.ElectaCourse.com
Instruments and TestingInstruments and Testing
ElectaCourse.com
© 2005
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 2/50
2
www.ElectaCourse.com
Installation Testing
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 3/50
3
www.ElectaCourse.com
REMEMBER
Visual inspection must precede all testing
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 4/50
4
www.ElectaCourse.com
REMEMBER
Dead testing precedes
Testing
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 5/50
5
www.ElectaCourse.com
Dead Testing
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 6/50
6
www.ElectaCourse.com
Isolate
before carrying
out dead tests
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 7/50
7
www.ElectaCourse.com
Approved voltage indicator
to GS 38
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 8/50
8
www.ElectaCourse.com
Maximum of 4mm on exposed prods
Preferably not more than 2mm
Fused leads
Finger guards
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 9/50
9
www.ElectaCourse.com
Continuity Testing
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 10/50
10
www.ElectaCourse.com
Continuity
Low-resistance
ohmmeter
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 11/50
11
www.ElectaCourse.com
Battery operated instrument
Low voltaged.c.d.c.
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 12/50
12
www.ElectaCourse.com
200 mA
4-24V
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 13/50
13
www.ElectaCourse.com
Verifying Continuity
Method 1
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 14/50
14
www.ElectaCourse.com
CautionSupply must be isolated
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 15/50
15
www.ElectaCourse.com
Temporary Link
Instrument
measures (R1+R2)
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 16/50
16
www.ElectaCourse.com
Along with verification of the cpc, state
the TWO other tests which are
automatically undertaken when carrying
out this test
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 17/50
17
www.ElectaCourse.com
The value of (R1 + R2)
Polarity
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 18/50
18
www.ElectaCourse.com
Unacceptable practice of connecting c.p.c.
to outgoing side of fuse or circuit breaker
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 19/50
19
www.ElectaCourse.com
Why is it unacceptable?
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 20/50
20
www.ElectaCourse.com
Unacceptable practice
of connecting c.p.c. to
outgoing fuse or circuit breaker way
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 21/50
21
www.ElectaCourse.com
Verifying Continuity
Method 2
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 22/50
22
www.ElectaCourse.com
CautionCautionSupply must be isolated
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 23/50
23
www.ElectaCourse.com
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 24/50
24
www.ElectaCourse.com
State TWO disadvantages of using
Method 2, as compared to Method 1
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 25/50
25
www.ElectaCourse.com
Use of long wander lead
Value of R2 only obtained
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 26/50
26
www.ElectaCourse.com
What consideration should be given to
the long wander lead?
Its resistance must be measured and
deducted from the measured value
of R2
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 27/50
27
www.ElectaCourse.com
Continuity of bonding
conductors
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 28/50
28
www.ElectaCourse.com
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 29/50
29
www.ElectaCourse.com
Why is it necessary to remove one end
of a bonding conductor when verifying
its continuity?
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 30/50
30
www.ElectaCourse.com
To avoid the possibility of parallel
earth paths
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 31/50
31
www.ElectaCourse.com
Break in c.p.c.
Parallel path
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 32/50
32
www.ElectaCourse.com
Continuity
of ferrous enclosures
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 33/50
33
www.ElectaCourse.com
Continuity of ferrous enclosures
• visual inspection
• low resistance ohmmeter
• high current test
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 34/50
34
www.ElectaCourse.com
High current test
25A
50 Volt maximum
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 35/50
35
www.ElectaCourse.com
High current-low-resistance
ohmmeter
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 36/50
36
www.ElectaCourse.com
Insulation Testing
Instrument must becapable of producing ashort-circuit current of 1mA
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 37/50
37
www.ElectaCourse.com
CautionCautionSupply must be isolated
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 38/50
38
www.ElectaCourse.com
Prior to insulation resistance testing
close main switch if testing from tails
fuses in circuit breakers closed
local switches closed/operate two-way
switches during test
neon's/capacitors disconnectedremove voltage sensitive equipment
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 39/50
39
www.ElectaCourse.com
Insulation resistance
testing between live
conductors
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 40/50
40
www.ElectaCourse.com
Insulation resistance
testing between liveconductors and earth
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 41/50
41
www.ElectaCourse.com
State the test voltage and minimum value of
insulation permitted for the following circuits
230V domestic lighting circuit
3 phase, 400V motor circuit
12V SELV circuit
750V discharge lighting circuit
50V FELV circuit
25V PELV circuit
500V - 0.5M
500V - 0.5M
250V - 0.25M
250V - 0.25M
1000V - 1.0M
500V - 0.5M
BS 7671 Table 71A - Page 172
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 42/50
42
www.ElectaCourse.com
Live Testing
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 43/50
43
www.ElectaCourse.com
Measurement of external impedance Ze
impedance
tester
Main switch
open
Earthing conductor
disconnected
.35
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 44/50
44
www.ElectaCourse.com
Why MUST the supply be isolated
before disconnecting the earthing
conductor?
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 45/50
45
www.ElectaCourse.com
Because if you don’t you could possibly kill
somebody. If there is a defect with the
insulation, and phase touches exposed
metalwork, the whole of the installationearthing could become live
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 46/50
46
www.ElectaCourse.com
State THREE other instances where
earth-fault loop impedance testing would
be required.
At the furthest point in every final circuit
At every distribution board
At every socket outlet
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 47/50
47
www.ElectaCourse.com
What precautions should be observed
when undertaking impedance tests withina circuit?
Ensure that persons or livestock arenot in contact with exposed metalwork
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 48/50
48
www.ElectaCourse.com
- - - - - - - - - - - - - - - - - - - - - - - - - - - - -
Measurement of prospective earth fault current
Prospective fault
current tester
Bonding conductors
connected
El t C
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 49/50
49
www.ElectaCourse.com
Measurement of prospective short circuit fault current
Prospective fault
current tester
El t C
8/10/2019 2391- Instruments &Testing
http://slidepdf.com/reader/full/2391-instruments-testing 50/50
50
www.ElectaCourse.com
Why is it necessary to verify the value
of prospective fault current at the originof an electrical installation?
To ensure the rated breaking capacity
of the main switch and overcurrent devices
are capable of breaking the prospective
fault current level