1 Clemson University Electric Power Research Association Zhenyu Fan IEEE Student Member Dynamic...

Post on 12-Jan-2016

217 views 3 download

Tags:

Transcript of 1 Clemson University Electric Power Research Association Zhenyu Fan IEEE Student Member Dynamic...

1Clemson University Electric Power Research Association

Zhenyu FanZhenyu Fan

IEEE Student MemberIEEE Student Member

Dynamic Performance of Distribution Systems with Distributed Generation

Adly A, GirgisAdly A, Girgis

IEEE FellowIEEE Fellow

2Clemson University Electric Power Research Association

OUTLINE

•Introduction

•Objectives

•Modeling and System description

•Simulation and Results

•Conclusions

3Clemson University Electric Power Research Association

Introduction

• Fault Analysis: a symmetrical component-based approach

• Induction Machine: widely used in the system

• DG (Photovoltaics) Modeling: power electronics related

4Clemson University Electric Power Research Association

• Fault analysis in distribution system with IM and DG(PV)

• The effects of DG(PV) in the faulted system

• The correct operation of DG and loads under the fault condition

Goals

5Clemson University Electric Power Research Association

Example system:

1

2

3

4 5 6 7

Subsystem 1

Subsystem 2

6Clemson University Electric Power Research Association

System Description by PSCAD

7Clemson University Electric Power Research Association

System Description by SIMULINK

8Clemson University Electric Power Research Association

Fault Analysis 1. Normal distribution system

Single phase A-ground fault (0.1-0.15 sec)Steady State

9Clemson University Electric Power Research Association

Fault Analysis 2. With Induction Motor

Single phase A-ground fault (0.1-0.15 sec) Disconnect IM after 0.45 secs Disconnect IM after 0.15 secs

10Clemson University Electric Power Research Association

Fault Analysis 3. With Photovoltaics

Single phase A-ground fault ( at 1.8 sec, PV disconnected from system at 1.9 sec)

11Clemson University Electric Power Research Association

Fault Analysis 4. With IM + PV (case 1)

Single phase A-ground fault ( at 1.7 sec, 1.73s(2 cycles) open breaker of Motor, 1.8s

disconnect PV, 1.9s fault cleared )

12Clemson University Electric Power Research Association

Fault Analysis 4. With IM + PV (case 2)

Single phase A-ground fault ( at 1.7 sec, 1.73s open breaker of PV, 1.8s disconnect Motor,

1.9s fault cleared )

13Clemson University Electric Power Research Association

050

100150200

Computing time

1 2 3 4

Different Systems

Comparison of two softwares

PSCAD

SIMULINK

Comparison of Matlab/Simulink and PSCAD

14Clemson University Electric Power Research Association

Conclusions

• The waveform of the fault current and voltage become worse because of the induction machine.

• PV generated the harmonics into system, so some filters are needed.

• During the fault, DG should be tripped before the fault is cleared.

• The accurate operation and smart control of DG and loads

can damp the oscillation and make the system stable.

15Clemson University Electric Power Research Association

Thank you!