REINFORCED AND PRESTRESSED CONCRETE PIPE, STEEL CYLINDER TYPE
Module 3a:Tests on installed pipeline
(summary)
UNE-EN 805 Standard: Water supply.Requirements for systems and components outside buildings.
Instruction of the Eduardo Torroja Institute for reinforced or prestressed concrete pipes of Septiembre 2007 that follows and meets current European standards.
AFTHAP m3a abreviado 10.03 2
Standards
Calculated water hammer:
STP = MDP + 100 kPa = MDP + 1 atm
Not calculated water hammer the lowest of the following values:
- STP = MDP x 1,5
- STP = MDP + 500 kPa = MDP + 0.5 atm
AFTHAP m3a abreviado 10.03 3
Not calculating the water hammer increases pipes, anchorages, enclosures and so, considerably
TEST PRESSURE
Water supply
The amount of water that is neccessary to pump in order to hold the pressure for one hour is measured
Pressure loss
The pressure loss is measured for one hour
AFTHAP m3a abreviado 10.03 4
Test methods
AFTHAP m3a abreviado 10.03 5
Rw
max EeID
E1
ΔpV1,2ΔV
The admissible value of the water supply, at the end of the test, must not exceed the value of DV max
V --- volume of the pipeline stretch that is being tested in litres∆p --- admissible pressure loss, in kPa (20 kPa)Ew --- water modulus of elasticity, in kPaID --- inside diameter of the pipe, in meters e --- pipe wall thickness, in metersER --- tranversemodulus of elasticity of the pipe wall, in kPa1,2 --- correction factor (for example for residual air) during the pressure main test
PRUEBA THPCCJE VOLUMEN DE AGUA (LITROS)
3400
2100
1400
980 1040
450270 220 150 180
200
500
1000
1500
2000
2500
3000
3500
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Acceptance – reject criteria. Water supply method
La duración de la prueba de caída de presión debe ser de 1 hora, o de mayor duración si así lo especifica el proyectista.
Durante la prueba, la caída de presión ∆P debe presentar una tendencia regresiva y al finalizar la primera hora no debe exceder
de 20 kPaAFTHAP m3a abreviado 10.03 6
PRUEBA THPCCJE CICLOS PRESIÓN (EJEX-HORAS / EJEY- PRESION EN ATM)
0,6
6
3,8
2,7
6
4,5
3,93,53,4
6
54,6
6
4
6,5
4,9
6,5
5,45,14,94,8
6,5
5,7
6,5
5,9
6,5
5,3
5,9
6
6,16,5
0
1
2
3
4
5
6
7
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
Acceptance – reject criteria. Pressure drop method
AFTHAP m3a abreviado 10.03 7
The test step by step
Type of pipe, material and joint
Diameter
Pressure
Length of the test stretches
constrution planning – logistics – temporal occupancy
pressure variation inside the stretch
water availability – water diversion between stretches
leveraging of valves, definitive anchorages and so.
hard searching of possible failures
AFTHAP m3a abreviado 10.03 8
Points of attention
Surge pressures and negative pressures, water hammer
Air removal – provisional assembly
Pipeline closing and trenche filling
Anchorage of special elements
(elbows, bifurcations, valves)
AFTHAP m3a abreviado 10.03 9
Test bulkheads and their anchorages
Points of attention
AFTHAP m3a abreviado 10.03 10
Elements of anchorage laid out and with the proper safety
Air outlets operational (air valves can be removed during the filling of the pipe, not during the test)
Filling that favours, or at least that allows air exit (slow and from the bottom if possible)
Keep the pipe full and with pressure until concrete saturation (see tables of losses)
Control of anchorages during the test
AFTHAP m3a abreviado 10.03 11
Test of a stretch